sales@elpowersystems.in 08588868905/06

TTA Panels

Drawout MCC Panels

Stainless Steel Panels (SSP)

Marshalling Kiosk

Main LT Panels (PCC)

Motor control centre

Synchronization Panels

AMF Panels

Controls Consoles

Meter Panel/Boxes

Feeder Pillars

PDB /LDB

Raising Main /
Bus Ducts

Automatic Power Factor Correction Panels

Sandwich Busbar trunking systems / Air Insulated

Salient Features

  • Modular Enclosure systems
  • Enclosure made from 2/1.6mm CRCA sheet
  • Fixed & Draw out type design
  • Available in "Form 1, 3, 4 "
  • Powder Coated in various colours
  • Spacious cable chambers facilitation easier cable termination and future maintenance.
  • Electrolytic grade High conductive aluminum/ Copper Bus Bar, with adequate cross section to ensure low operating temperature.
  • Busbars Insulated with red, yellow, blue and black colored PVC heat shrinkable sleeves for easy identification.
  • Extendable Bus bar
  • Non - hygroscopic, SMC insulators, with anti-tracking barriers for Bus Bar
  • Type tested with CPRI


Construction Type

Elpower-22-single front, rear dead (front access only) Elpowe-22-01-single front, rear access Elpower-22-02-double front

Salient Features
• Spacious arrangement is made for cable termination ensuring comfortable operation & easy maintenance.
• Bolted modular construction facilities modification, retrofitting, extensibility in minimum possible time.
• Use of quarter turnkey flush type steel door locks for convenient operation.
• Each panel is provided with plastic drawing pocket to house relevant drawings.
• Metallic/transparent barriers are provided, within the cubicle for prevention of human contact with live part accidentally
• All covers, doors inter panel jointing are provided with neoprene gasket for perfect dust protection.
• A perfect compartmentalized construction.
• High quality epoxy powder coated switch boards to with stand corrosive environment and long lasting elegant door.
• Specially designed concealed profile of neoprene is used for gasketing to ensure dust protection.

Painting

After perfect chemical pretreatment as per IS-6005, the fabricated components are painted in a CONVEYRISED POWDER COATING PLANT with high quality epoxy polyester powder, thus giving a long life to panel and good aesthetics.

The standard finish is SIEMENS PABBEL GREY (RAL 7032/RAL 7035) mounting arrangement in ORANGE (RAL2000)

Busbars

Copper/Aluminum bus bar of EC91E ELECTROLYTIC GRADE is procured from Reputed Manufacturer and cross sectional area is chosen on basis of bus bar calculation considering derating factors

• Bus bars are braced rigidly to withstand short circuit fault with SMC supports and proper bracing housed in electroplated “u” shaped channels. ELPOWER SYSTEMS

• All bus bars are insulated with PVC heat shrinkable sleeves of relevant color.

• Earth bus bar size is determined with earth fault calculation and run throughout the panel and connected with every door/ clamp of metallic switch gear body mounted. Assembling

Wiring

ELPOWER has developed a modern wiring shop with highly skilled wire-men and precision tools.

• Safe wiring is laid down by using plastic grommet and flexible conduits.
• Excellent dressing with proper printed ferrule.
• Wiring is bunched nicely with the PVC duct, also loose wiring in plastic spiral.

Testing

Type - Testing

Panel designing has been verified by the following “CPRI” tests as per IS-8623, IEC439,EN60439.

o SHORT CIRCUIT TEST 50 KA FOR 1 SEC
o TEMPERATURE RISE TEST +35°C OVER AMBIENT
o INGRESS PROTECTION-IP-55

In - House Testing

• Insulation with 1000 V Megger.
• High voltage Test at 2.5 KV for 1 sec (50Hz).
• Functional Test.
• Powder coating quality (1000 hr & scratch etc.).
• Al & Cu Conductivity (% IACS). KWH calibration.
• Primary injection up to 4000 A* Secondary injection.
• Switch gear operational tests